Why convert VA to amps
Transformers, UPS units, and inverters carry a VA rating because that’s the quantity their windings and internal wiring have to handle. But a circuit is defined in amps — the breaker, the wire, the receptacle. To know whether a piece of VA-rated equipment fits an existing circuit, or how much current it will draw at your voltage, you divide its VA by that voltage.
Because VA is apparent power, the power factor never enters this calculation. Volts times amps is VA, so amps is simply VA divided by volts. That’s also why transformer and UPS ratings are in VA in the first place: the figure stays valid no matter what the connected load’s power factor turns out to be.
The VA to amps formula
Single-phase:
Three-phase, line-to-line voltage:
Worked example
The calculator’s defaults are 2,400 VA on a single-phase 240 V circuit.
The load draws 10 A. Put the same 2,400 VA on a three-phase 240 V circuit and each line carries:
less than half, because the load is spread over three conductors instead of two.
VA to amps at common voltages (single-phase)
| VA | 120 V | 208 V | 240 V | 277 V |
|---|---|---|---|---|
| 500 | 4.2 A | 2.4 A | 2.1 A | 1.8 A |
| 1,000 | 8.3 A | 4.8 A | 4.2 A | 3.6 A |
| 1,500 | 12.5 A | 7.2 A | 6.3 A | 5.4 A |
| 3,000 | 25.0 A | 14.4 A | 12.5 A | 10.8 A |
| 5,000 | 41.7 A | 24.0 A | 20.8 A | 18.1 A |
Transformer current, both sides
A transformer’s VA is the same on the primary and the secondary, minus small losses. So the same rating gives you both currents: divide by the primary voltage for the input current, by the secondary voltage for the output current. A 1,000 VA 120/24 V control transformer draws about 8.3 A on its 120 V side and delivers about 41.7 A on its 24 V side.
What the result covers
This is the steady running current at the entered voltage. It doesn’t include the inrush a motor or transformer draws for the first cycle or two at power-up, and it assumes the supply holds at nominal voltage. For wire and breaker sizing, apply the continuous-load margin and derating rules from your local code on top of this figure.
Common mistakes
- Forgetting √3 for three-phase, which overstates the current by about 73%.
- Using the wrong voltage — current scales inversely with it.
- Adding a power factor. VA to amps doesn’t use one.
For the reverse, use the amps to VA calculator. For the kilovolt-amp scale, see kVA to amps, and for real power, VA to watts.