Skip to main content
Mathovia

Electrical

Three-Phase Power Calculator

Use this three-phase power calculator to estimate apparent power, active power, and reactive power from line voltage, line current, and power factor. It uses standard line-to-line voltage and line current formulas for balanced three-phase systems.

Apparent power
6,928.20 VA
Active power
5,542.56 W
Reactive power
4,156.92 var
PoorFairGoodExcellent0.8
Power factor sets how much of the apparent power (VA) turns into real work (W).
Written by
MPhil in Mathematics, Founder of Mathovia
Published

Mathematics verification: Mathematical formulas, calculations, worked examples and solutions are reviewed for accuracy before publication. How we check our work

Three-Phase Power Calculator formula
The Three-Phase Power formula

Three-Phase Power Calculation

A three-phase power system uses three alternating voltages that are separated by 120 electrical degrees. Compared with a single-phase system, three-phase power can deliver energy more smoothly and efficiently, which makes it common in motors, industrial equipment, commercial buildings, and electrical distribution systems.

This calculator estimates three important quantities. Apparent power describes the total electrical loading placed on the system and is measured in volt-amperes. Active power is the portion that performs useful work, such as turning a motor shaft or heating an element, and is measured in watts. Reactive power supports electric and magnetic fields in inductive and capacitive equipment and is measured in volt-amperes reactive.

The calculation assumes that the voltage entered is line-to-line RMS voltage and that the current entered is line current. The system should be balanced, and the power factor must be entered as a decimal rather than a percentage. For example, enter 0.8 instead of 80%. A common mistake is using phase voltage with the line-voltage formula, which produces an incorrect result unless the formula is adjusted for the wiring configuration.

How to Calculate Three-Phase Power (step by step)

Step One: Find Apparent Power

Calculate the total apparent power using the square root of three, line-to-line voltage, and line current.

Using the calculator’s default values:

√3 × 400 V × 10 A = 6,928.20 VA

Step Two: Find Active Power

Multiply apparent power by the power factor to determine the portion of power doing useful work.

active power = apparent power × power factor

Using the calculator’s default values:

6,928.20 VA × 0.8 = 5,542.56 W

Step Three: Find Reactive Power

Reactive power is calculated from the relationship between apparent power, active power, and reactive power.

Using the calculator’s default values:

√(6,928.20² − 5,542.56²) = 4,156.92 var

Understanding the Results

The default example produces 6,928.20 VA of apparent power, 5,542.56 W of active power, and 4,156.92 var of reactive power. These describe the same balanced load from three angles. Apparent power is what the transformer and feeder carry, active power is what a wattmeter reads and the utility bills, and reactive power is the part that circulates without doing work.

The three form a right triangle:

so VA, which matches the apparent-power result.

Three-Phase Power Calculator worked example diagram
A visual read of the worked example above — the same numbers the calculator returns for its default inputs.

Power factor and the reactive-power penalty

Power factorActive power (W)Reactive power (var)Line current (A)
1.006,928010.0
0.956,5822,16410.0
0.855,8893,65110.0
0.805,5434,15710.0
0.704,8504,94810.0

Every row carries the same 10 A and the same 6,928 VA. As the power factor drops, less of that becomes useful watts and more becomes reactive vars. Flip it around — hold the active power constant and a poor power factor forces the current up, which raises losses in the cable, widens the voltage drop, and eats transformer capacity. That’s why utilities meter reactive power for large customers and why power-factor-correction capacitors are standard on industrial switchboards.

Where three-phase power calculations come up

  • Motor and drive sizing — converting a mechanical kW rating into line current for cable and breaker selection.
  • Generator and UPS selection — matching a kVA source to a mixed motor-and-lighting load.
  • Transformer loading checks — adding up connected kVA against a transformer’s nameplate.
  • Energy audits — separating the billed kW from the kVA the site actually draws.

Common mistakes

  • Using line-to-neutral voltage with the line-to-line formula, which understates power by √3.
  • Entering power factor as a percentage (80 instead of 0.8).
  • Applying the balanced formula to a clearly unbalanced panel, where phase-by-phase math is needed.
  • Forgetting harmonic loads. Drives and rectifiers distort the current waveform, and true power then needs a real measurement, not this sinusoidal formula.

For the single-phase equivalents, see the volts to watts calculator and amps to kVA. To size a supply for a motor, horsepower to kVA covers the motor side.

Frequently Asked Questions

What is the three-phase power formula?+

With line-to-line voltage and line current in a balanced system: apparent power S = √3 × V × I, active power P = √3 × V × I × PF, and reactive power Q = √(S² − P²).

Why the √3 factor?+

The three line currents are 120° apart in time, so they don't add arithmetically. When you work the vector math for a balanced load using line-to-line voltage and line current, the total power comes out to √3 (about 1.732) times their product, not 3 times.

What's the difference between active, reactive, and apparent power?+

Active power (watts) does work. Reactive power (vars) sloshes between the source and the load's magnetic or electric fields without doing work. Apparent power (VA) is the vector sum of the two and represents the total loading the wiring and source carry.

Line-to-line or line-to-neutral voltage?+

This calculator's formula expects line-to-line voltage (400 V, 480 V, 208 V). If you have line-to-neutral (phase) voltage, either multiply it by √3 first, or use the alternative form P = 3 × V_phase × I_phase × PF.

Does it handle unbalanced loads?+

No. It assumes a balanced system with clean sine waves. For an unbalanced load, calculate each phase separately and add, or measure with a three-phase power analyzer.

How do I get line current from a motor's kW rating?+

Rearrange the active-power formula: I = P ÷ (√3 × V × PF). A 15 kW motor at 400 V and 0.85 power factor draws about 25.5 A per line.

Related calculators