Why this conversion matters
Generators, transformers, UPS units, and service panels are rated in kVA — apparent power. Breakers, conductors, and disconnect switches are rated in amps. To connect a kVA-rated piece of equipment to a real circuit, you have to turn its kVA rating into a current, and that needs the voltage and whether the system is single- or three-phase.
The useful thing about working from kVA rather than kW is that power factor drops out. Apparent power already bundles the reactive current in with the working current, so the amps that flow in the wire depend only on the kVA and the voltage. That’s exactly why transformers carry a kVA rating in the first place: their limiting factor is winding heat, which is set by current, no matter what the power factor of the load turns out to be.
The kVA to amps formula
Single-phase:
Three-phase, using line-to-line voltage:
Worked example
The calculator’s defaults are 5 kVA on a single-phase 240 V circuit.
Convert to volt-amps:
Divide by the voltage:
So each conductor carries about 20.8 A. On the same 5 kVA at 240 V three-phase, the current per line drops to 5,000 ÷ (1.732 × 240) ≈ 12.0 A, because the load is spread over three wires instead of two.
kVA to amps at common voltages (single-phase)
| kVA | 120 V | 208 V | 240 V | 480 V |
|---|---|---|---|---|
| 1 | 8.3 A | 4.8 A | 4.2 A | 2.1 A |
| 5 | 41.7 A | 24.0 A | 20.8 A | 10.4 A |
| 10 | 83.3 A | 48.1 A | 41.7 A | 20.8 A |
| 25 | 208 A | 120 A | 104 A | 52.1 A |
| 50 | 417 A | 240 A | 208 A | 104 A |
For three-phase, divide any value in the table by 1.732.
What the result does and doesn’t cover
This is the steady, balanced running current. It doesn’t include the inrush a motor or transformer pulls at startup, which can be several times higher for a fraction of a second. It also assumes the three phases are evenly loaded — an unbalanced panel will run more current on one line than this figure suggests. Size conductors and overcurrent protection from the equipment’s nameplate full-load amps and the ampacity tables, using this number as a cross-check.
Common mistakes
- Forgetting the √3 for three-phase, which overstates the current by about 73%.
- Using line-to-neutral voltage where line-to-line belongs in the three-phase formula.
- Applying a power factor. kVA to amps doesn’t use one; power factor only matters when converting to kW or watts.
For the reverse, use the amps to kVA calculator. To find the real power behind the apparent power, see kVA to kW, and for the working current of a kW-rated load, kW to amps.