Skip to main content
Mathovia

Electrical

Voltage Drop Calculator

Enter the run length one way, the load current, the conductor and the supply voltage. The result shows the drop in volts, the percentage, and the longest run that stays inside the 3 percent recommendation.

Voltage drop
4.97 V
Voltage drop
2.07 %
Voltage at the load
235.03 V
Longest run within 3%
145 ft
Within 3%3–5%Over 5%2.07 %
Percentage drop against the NEC 3 percent branch-circuit recommendation.

Voltage drop = (2 × K × I × L) ÷ CM for single phase, or (1.732 × K × I × L) ÷ CM for three phase. K is 12.9 for copper and 21.2 for aluminium, L is the one-way length in feet, and CM is the conductor's area in circular mils.

Written by
MPhil in Mathematics, Founder of Mathovia
Published

Mathematics verification: Mathematical formulas, calculations, worked examples and solutions are reviewed for accuracy before publication. How we check our work

Every conductor is a resistor. Push current down a hundred feet of 12 AWG and some of your supply voltage is spent heating the cable instead of arriving at the load. On a short kitchen circuit that loss is invisible; on a run out to a workshop it is the difference between a table saw that starts cleanly and one that groans, stalls and eventually cooks its own windings.

Voltage Drop Calculator formula
The Voltage Drop formula

The voltage drop formula

is the conductor’s resistivity constant — 12.9 for copper, 21.2 for aluminium, both in ohm-circular-mils per foot. is the load current in amps, is the one-way run length in feet, and is the conductor’s cross-sectional area in circular mils.

The 2 is there because current has to make a round trip. You measure the distance from the panel to the load once, and the formula accounts for the return conductor.

For a three-phase circuit the geometry changes and the factor becomes :

That is why three-phase distribution suffers noticeably less drop than single phase for the same power delivered — one of several reasons it is used for long runs and large loads.

Worked example

A 20-amp circuit feeding a detached garage, 100 feet from the panel, wired in 10 AWG copper on a 240-volt supply.

Step 1 — look up the conductor area. 10 AWG is 10,380 circular mils.

Step 2 — substitute into the single-phase formula.

Step 3 — express it as a percentage of the supply.

Step 4 — check it against the recommendation. 2.07 percent is inside the 3 percent target, so 10 AWG is the right choice here.

The load sees volts. That is a drop nothing on the circuit will notice.

Voltage Drop Calculator worked example diagram
A visual read of the worked example above — the same numbers the calculator returns for its default inputs.

What happens if you drop to 12 AWG

Same run, same load, one gauge smaller:

Over the limit — and on a 120-volt supply the same 7.90 volts would be 6.58 percent, which is genuinely bad. This is the single most useful thing the formula tells you: drop in volts does not care about supply voltage, but drop as a percentage halves when you double the voltage. Running an outbuilding at 240 V instead of 120 V solves most long-run problems on its own.

Longest run within 3 percent

Rearranged for length, the formula answers the question people actually have:

At 20 amps on a 240-volt single-phase circuit in copper:

WireCircular milsMax run at 3%
14 AWG4,10757 ft
12 AWG6,53091 ft
10 AWG10,380145 ft
8 AWG16,510230 ft
6 AWG26,240366 ft
4 AWG41,740583 ft

Halve every figure for a 120-volt circuit, because the allowed drop in volts halves with it. Multiply by roughly 0.61 for aluminium.

The 3 and 5 percent figures

These come from informational notes in the National Electrical Code, not from enforceable articles. Article 210.19(A) suggests 3 percent maximum on a branch circuit, and 215.2(A) suggests 5 percent for the feeder and branch circuit combined.

CircuitRecommended maximum
Branch circuit alone3%
Feeder alone3%
Feeder plus branch, total5%

Because they are recommendations rather than requirements, an inspector cannot usually fail an install on drop alone. Equipment manufacturers are less forgiving: most motors are rated for ±10 percent of nameplate voltage, and running persistently near the bottom of that band shortens their life.

Why oversizing for drop is not the same as sizing for ampacity

Two different constraints, and both have to be satisfied.

Ampacity is about heat in the conductor and its insulation. It sets the minimum legal size for a given load and is a hard code requirement — 12 AWG copper for a 20-amp circuit, for example. The wire gauge calculator covers this side.

Voltage drop is about performance at the far end. It can push you above the ampacity minimum on a long run, but it can never let you go below it.

So on the garage example, 12 AWG is legal for 20 amps and 10 AWG is chosen purely for drop. That is the normal situation on any long run: ampacity sets the floor, drop sets the answer.

Ways to fix an excessive drop

ChangeEffect on drop
One AWG size largerroughly 20% less
Two AWG sizes largerroughly 37% less
Double the circular milsexactly half
Copper instead of aluminiumroughly 39% less
240 V instead of 120 Vpercentage halves
Halve the run lengthexactly half

Raising the voltage is usually the cheapest fix by a wide margin, because it improves the percentage without a single extra pound of copper. Splitting one long circuit into two shorter ones helps as well, since each carries less current.

Common mistakes

  • Doubling the distance yourself. The formula’s 2 already accounts for the return path. Enter the one-way length.
  • Using 1.732 on a single-phase circuit. That understates the drop by about 13 percent.
  • Using AWG numbers directly. The formula needs circular mils. 12 AWG is 6,530 cmil, not 12.
  • Sizing on drop alone. Ampacity is the code minimum and comes first.
  • Forgetting aluminium’s penalty. Same gauge, about 64 percent more drop.
  • Calculating at nameplate rather than actual load. For motors, use the running current, but check the starting surge too — inrush can be six times the running figure and that is what causes visible light flicker.

For picking the code-minimum size in the first place, use the wire gauge calculator. For the underlying relationship between volts, amps and resistance that this formula is built on, see the Ohm’s law calculator.

About the formula: Voltage drop = (2 × K × I × L) ÷ CM for single phase, or (1.732 × K × I × L) ÷ CM for three phase. K is 12.9 for copper and 21.2 for aluminium, L is the one-way length in feet, and CM is the conductor's area in circular mils.

Frequently Asked Questions

How do you calculate voltage drop?+

Use for a single-phase circuit. K is 12.9 for copper, I is the load current in amps, L is the one-way run length in feet, and CM is the conductor's circular mils. For three phase, swap the 2 for 1.732.

What is an acceptable voltage drop?+

The NEC recommends no more than 3 percent on a branch circuit and 5 percent total from the service to the furthest outlet. Both figures are informational notes rather than enforceable rules, but inspectors and equipment manufacturers treat them as the target.

Why do I use the one-way distance and then multiply by 2?+

Because current travels out along one conductor and back along the other, so the circuit length is twice the run. The 2 in the formula does that for you, which is why you measure the distance from panel to load once rather than doubling it yourself.

Does voltage drop matter on a short run?+

Rarely. Drop is proportional to length, so a 15-foot run has a tenth of the drop of a 150-foot one at the same current. It becomes a real design constraint on outbuildings, well pumps, long garage circuits and anything fed from a subpanel across a property.

How do I reduce voltage drop?+

Increase the conductor size — it is the only variable you can usually change. Doubling the circular mils halves the drop. The other levers are raising the supply voltage, shortening the run, or splitting the load across two circuits.

Is aluminium wire worse for voltage drop?+

Yes, for a given size. Aluminium's K value of 21.2 against copper's 12.9 means about 64 percent more drop in the same gauge. That is why aluminium feeders are typically sized two AWG steps larger than the copper equivalent for the same job.

What happens if voltage drop is too high?+

Motors run hot and start sluggishly, incandescent lamps dim, heaters take longer, and electronics with switching supplies draw more current to compensate — which increases the drop further. Persistent under-voltage shortens the life of motors in particular.

Related calculators